Surge Protection and Surge Immunity Testing Facility

Standards Followed :
- IEC 61643-11 Low – Voltage surge protective devices-Part11: Surge protective devices connected to low-voltage power systems-Requirements and test methods-Edition 1.0 2011-03
- IEC 61643-21: Low – Voltage surge protective devices-Part21: Surge protective devices connected to telecommunications and signaling networks-Performance requirements and testing methods.-Edition 1.1 2009-04
- IEC 61000-4-5: Electromagnetic compatibility (EMC)-Part 4-5: Testing and measurement techniques-Surge immunity test
Test carried out :
Testing of Surge Protective Devices
Measurement of Limiting Voltage of Surge Protective Devices (SPDs) Connected to Low Voltage Power Distribution Systems.
- Testing of 230V/ 3-wire SPDs for all modes of protection(L-N, L-G, N-G) at one test level only.
- Testing of 415V/ 5-wire SPDs, for one phase between Phase-N, Phase-G & N-G at one test level only.
Measurement of Limiting Voltage of Surge Protective Devices (SPDs) Connected to Low Voltage Power Distribution Systems as per Testing Methods Specified in IEC 61643-11
- Testing of 230V/3-wire SPDs for one mode of protection (eg. L-N).
- Testing of 3-wire SPDs for 2 modes of protection (L-N, L-G).
- Testing of 3-wire SPDs for all modes of protection (L-N, L-G, N-G).
- Testing of 415V/ 5-wire SPDs, separately between each phase and neutral.
- Testing of 415V/ 5-wire SPDs, separately between each Phase-N,Phase-G & N-G.
Measurement of Limiting Voltage of Surge Protective Devices (SPDs) Connected to Telecommunication and Signaling Networks as per Testing Methods Specified in IEC 61643-21
- Measurement of Impulse-limiting voltage as per IEC 61643-21 with 1.2/50 us, 8/20 us combination waveform, 5 pulses from each polarity
Surge Immunity Testing of Electrical Appliances
- Testing of equipment/devices with 1.2/50 µs, 8/20 µs Combination wave.
- Testing of equipment/devices for surge immunity as per test routines recommended in IEC 61000-4-5.